CBETA Equipment Protection System

*Responsible personnel: Nalanjan Banerjee, Adam Bartnik, John Dobbins, Karl Smolenski, Rob Michnoff, and others
*Date: February xx, 2019

Overview

The specific equipment protection system requirements, operational details and system testing is separately defined for each intended mode of operation.

A detailed document describing the CBETA equipment protection system is available at the following link:

Permanent Magnet Protection

In order to protect the Halbach permanent magnets in the FFA loop from demagnitization, beam losses on any individual magnet must be limited to less than 100 pA continuous current.

Modes of Operation

These are the current modes of operation, set automatically in EPICS under the variable EPSSTE01_state.
Index Name Description Max I Max Q Period N bunches
-1 Undefined Error state 0 0 1 s 0
0 MACHINE OFF Interlocks are not set, machine is off N/A N/A 1 s 200,000
1 ZERO CHARGE MODE Laser power low, up to 100% duty factor 1 uA 25 fC 1 s 42,000,000
2 Gun-ICM Only beam ends at MA3DPA01, used for phasing the ICM 1 uA 5 pC 1 s 200,000
3 Diagnostic Line (Slits IN)
6 MeV beam through diagnostic line, beam lost on shielded slits 1 uA 5 pC 1 s 200,000
4 Diagnostic Line (Slits OUT) 6 MeV beam through diagnostic line, beam lost at end of line 100 nA 5 pC 1 s 20,000
5 MLC OFF Beam through MLC, but no cavities enabled 100 nA 5 pC 1 s 20,000
6 MLC (Single Cavity) Single cavity operation, phasing / calibration 100 nA 5 pC 1 s 20,000
7 MLC
Many cavity operation 10 nA 5 pC 1 s 2,000
8 Dump Line Beam enters dump line at 6 MeV 100 nA 5 pC 1 s 20,000
9 S1 Splitter Beam in S1 line, but not into the FFA line 10 nA 5 pC 1 s 2000
10 FFA Arc Beam into the FFA line 5 nA 5 pC 1 s 1000

List of rules for each mode

-1 : Undefined

  • This state occurs when none of the other states are valid. It should not happen in normal operation

0 : MACHINE OFF

  • PPSMRC00_led.RVAL == 0

1 : ZERO CHARGE MODE

  • | MA3DPA01 _cmd | < 0.1 amps
  • LLRLDM01_low_on_led == 1

2 : Gun-ICM Only

3 : Diagnostic Line (Slits IN)

4 : Diagnostic Line (Slits OUT)

5 : MLC OFF

  • MA3DPA01 _cmd < 0.1 amps
  • | MS1DIP01 _cmd | <= 0.5
  • Number of MLC cavities not tripped == 0

6 : MLC (Single Cavity)

  • MA3DPA01 _cmd < 0.1 amps
  • | MS1DIP01 _cmd | <= 0.5
  • Number of MLC cavities not tripped == 1

7 : MLC

  • MA3DPA01 _cmd < 0.1 amps
  • | MS1DIP01 _cmd | <= 0.5
  • Number of MLC cavities not tripped > 1

8 : Dump Line

  • Not implement yet

9 : S1 Splitter

10 : FFA Arc

Description of test

Confirm that all EPICS IOC names communicate with the defined hardware module.

Test Procedure

  • Open the EDM screen xxxxx
  • Click on XXX to do something important
  • Provide embedded pics if needed and links to spreadsheet lists or other details
  • Do this that and other stuff
    • Expected result: xxxxxxx
  • Do more important stuff
    • Expected result: xxxxx

Actual results

(02/xx/2019, name) As expected or explain what did not operate as expected
  • links to related details

Problems found

  • List any problems

Other notes

  • blah blah blah

-- RobMichnoff - 12 Feb 2019